H12-425_V2.0 HCIP-Data Center Facility Deployment V2.0 Questions and Answers

Questions 4

If multiple SmartLi battery cabinets are combined, press and hold the POWER ON/OFF button on each battery management module for more than 2s, and then switch on the battery circuit breaker in any cabinet to start all battery cabinets.

Options:

A.

True

B.

False

Buy Now
Questions 5

Which of the following methods can be used to open the access control for the FusionModule2000 smart module?

Options:

A.

Fingerprint

B.

Card reader

C.

Password

D.

Facial recognition

Buy Now
Questions 6

The UPS5000-E-200K works in normal mode. If two ECMs are faulty, how does the UPS work?

Options:

A.

The UPS has no output.

B.

The UPS transfers to bypass mode.

C.

The LCD is off, but the UPS still works in normal mode.

D.

The UPS switches to battery mode.

Buy Now
Questions 7

When connecting chilled water pipes for the NetCol8000-C, fill water and preserve pressure 8 hours after the conversion adapter is connected.

Options:

A.

True

B.

False

Buy Now
Questions 8

The ECC800-Pro is the core component for FusionModule2000 local management. Southbound components can be using the PoE bus.

Options:

A.

True

B.

False

Buy Now
Questions 9

When the outdoor unit of a Huawei air-cooled air conditioner is installed horizontally, what is the minimum distance between the outdoor unit and the wall or obstacle?

Options:

A.

100 mm

B.

200 mm

C.

300 mm

D.

600 mm

Buy Now
Questions 10

Smart ETH gateways cannot be cascaded.

Options:

A.

True

B.

False

Buy Now
Questions 11

Which of the following is a standard component in the FusionModule800 typical configuration?

Options:

A.

PAD

B.

Video surveillance system

C.

Intelligent lock

D.

iBattery

Buy Now
Questions 12

During filling refrigerant for NetCol5000-A, there is no need to put the refrigerant steel cylinder upside down on balance.

Options:

A.

True

B.

False

Buy Now
Questions 13

The power system of a UPS2000-G-15K at a site is three-phase input and single-phase output. After installation, it is found that the mains and bypass inputs are three-phase, the output is single-phase, and the mains and bypass inputs share a power source. Which of the following statements are true about the UPS wiring mode?

Options:

A.

The wiring mode is incorrect, if the upstream mains input switch is turned on, the UPS will be short-circuited and damaged immediately.

B.

The wiring mode is correct. The UPS can start properly.

C.

The wiring mode is incorrect. The UPS cannot work in battery mode, but can still work in bypass mode or inverter mode.

D.

The wiring mode is incorrect. The correct wiring mode should be single-phase bypass input, three-phase mains input, and one power source.

Buy Now
Questions 14

Which of the following statements is false about the ECM of the UPS5000-E?

Options:

A.

As a control interface for the entire system, the ECM communicates with each module and provides a bus for communication between the dry contact card and the system control card.

B.

The ECM controls the bypass module to work properly, if one ECM is faulty, the UPS can still work in normal mode but cannot be manually switched to bypass mode.

C.

The ECM ensures equalized output currents between modules so that load power is equally shared.

D.

The ECM provides three types of CAN communication: monitoring CAN communication, intra-rack parallel CAN communication, and inter-rack parallel CAN communication.

Buy Now
Questions 15

As the altitude increases, the air density decreases, and the heat exchange capability of the air in a unit volume decreases. In this case, NetCol8000-E220 works with derating.

Options:

A.

True

B.

False

Buy Now
Questions 16

In the FusionModule800 grounding solution, each cabinet is connected to the ground bar of the data center.

Options:

A.

True

B.

False