CDCS EXIN EPI Certified Data Centre Specialist Questions and Answers

Questions 4

The humidity in the computer room has increased from about 60% up to 85% Relative Humidity (RH). What potential risk does this pose to your equipment?

Options:

A.

No risks at all

B.

The risk of excessive wear and corrosion will increase

C.

The electrostatic discharge (ESD) levels will go up

D.

There will be a cooling risk due to a high wet bulb temperature

Buy Now
Questions 5

An air-conditioner unit needs to be selected. Two types are available:

Unit-A has a Sensible Heat Ratio (SHR) of 0.7.

Unit-B has a Sensible Heat Ratio (SHR) of 0.9.

From an efficiency point of view, which one should be selected?

Options:

A.

It does not matter, as the Sensible Heat Ratio has nothing to do with efficiency.

B.

Not relevant, as Sensible Heat Ratio is only specified for air-conditioner equipment to indicate the ratio between intake temperature and exhaust temperature.

C.

Unit A

D.

Unit B

Buy Now
Questions 6

Where should raised-floor installation start?

Options:

A.

Point A (entrance corner)

B.

Point B (side wall)

C.

Point C (center of the room)

D.

Point D (corner opposite entrance)

Buy Now
Questions 7

The building in which the computer room is housed is required to have a sprinkler system. The building is therefore equipped with a wet pipe system.

What action, if any, should you recommend for the computer room?

Options:

A.

Maintain the current wet pipe system.

B.

Replace the wet pipe system with a deluge system.

C.

Replace the wet pipe system with a dry pipe system.

D.

Replace the wet pipe system with a pre-action system.

Buy Now
Questions 8

It is assumed that EMF shielding material must be installed as the EMF levels coming from the transformer room into the computer room are measured at 100mG. The transformer room is approximately 10 meters away from the computer room and is separated by a corridor. You can assume that no physical issues are present for installing shielding material at any area/location.

Where should you recommend the shielding material to be installed?

Options:

A.

As close as possible to the computer room

B.

As close as possible to the transformer room

C.

It does not matter, either close to the transformer room or the computer room is okay as there is no impact to cost or shielding material performance

D.

Shielding is not required to be installed as 100mG is within the acceptable levels for computer rooms

Buy Now
Questions 9

What is the floor loading requirement for a Rated-3 data center according to ANSI/TIA-942?

Options:

A.

7.2 kPa

B.

8.4 kPa

C.

12 kPa

D.

15 kPa

Buy Now
Questions 10

What should be implemented when an Inergen-based fire suppression system is installed in the computer room?

Options:

A.

Drainage system under raised floor

B.

Gas tanks need to be within or close to the data center

C.

Pressure release valves in the data center

D.

Proper water leak detection system

Buy Now
Questions 11

When designing a data center network, your company wants to minimize the number of network switches to manage.

What type of physical cabling layout would be the best choice?

Options:

A.

ToR (Top of Rack) design

B.

EoR (End of Row) design

C.

Star network design using coaxial cables

D.

It does not matter as the number of switches is not influenced by the physical cabling layout

Buy Now
Questions 12

What is a potential disadvantage of using a hypoxic-based fire suppression system as a fire extinguishing system?

Options:

A.

It can only be used in computer rooms which have sufficient air changes per hour.

B.

The gas containers need to be close to the hazard area.

C.

It can only be used in non-continuous occupied areas.

D.

It can only be used in computer rooms where you have sufficient positive pressure.

Buy Now
Questions 13

What is the preferred way to measure dust levels in the computer room?

Options:

A.

With an air particle hand-held analyzer

B.

With test coupons

C.

By taking dust samples under the raised floor

D.

By opening up equipment for inspection

Buy Now
Questions 14

What is the sensible heat ratio (SHR)?

Options:

A.

Ratio of the sensible heat to the total of sensible plus latent heat to be removed from a conditioned space

B.

Ratio of the latent heat to the total of sensible plus latent heat to be removed from a conditioned space

C.

Ratio of cold-air supply to hot-air return temperature of a cooling system

D.

Ratio of the cold-aisle temperature to the hot-aisle temperature

Buy Now
Questions 15

A battery bank has 800 Ah total capacity. How much charging current should the rectifier be able to supply?

Options:

A.

40 A

B.

60 A

C.

80 A

D.

160 A

Buy Now
Questions 16

Racks with 1.0 m depth and cold aisle containment with 3 perforated tiles are used. What aisle pitch is recommended?

Options:

A.

5 tiles pitch rule

B.

7 tiles pitch rule

C.

8 tiles pitch rule

D.

10 tiles pitch rule

Buy Now
Questions 17

The noise levels in the data center are approximately 91 dB (A).

Do employers need to take precautions?

Options:

A.

No, anything less than 100 dB (A) is acceptable.

B.

There are no regulations regarding noise levels inside a building. Regulations only apply to noise pollution outside of the building.

C.

As long as the data is compliant to ISO/IEC 27001 it is acceptable.

D.

Yes, since it is mandated by regulations.

Buy Now
Questions 18

What is needed to determine the Relative Humidity (RH)?

Options:

A.

Wet bulb temperature, local atmospheric pressure, and calculator

B.

Dry bulb temperature, airflow, and conversion table

C.

Cold surface with dew collection counter

D.

Dry bulb temperature, wet bulb temperature, and psychrometric chart

Buy Now
Questions 19

A sprinkler system employs automatic sprinklers attached to a piping system containing water and connected to a water supply so that water discharges immediately when a head opens. What is this called?

Options:

A.

Dry pipe system

B.

Deluge system

C.

Pre-action system

D.

Wet pipe system

Buy Now
Questions 20

What is the first step in the design stage of the data center life cycle?

Options:

A.

Select vendors

B.

Do a design validation

C.

Define the scope of the project

D.

Freeze the design

Buy Now
Questions 21

The building requires sprinklers and is equipped with a wet-pipe system. What action should you recommend for the computer room?

Options:

A.

Maintain the current wet-pipe system

B.

Replace the wet-pipe system with a deluge system

C.

Replace the wet-pipe system with a pre-action system

D.

Replace the wet-pipe system with a dry-pipe system

Buy Now
Questions 22

In order to save energy, you are going to install an automated system to switch off lights. What should be taken into consideration when installing such a system?

Options:

A.

Security guards should perform regular inspections verifying the system works.

B.

The system should not be based on motion detection as the lights might suddenly switch off while staff is still at work.

C.

It is not advisable to use such a system since it will reduce the lifetime of LED lighting.

D.

At all times, the levels should allow for security cameras to function properly.

Buy Now
Questions 23

What is the minimum requirement for power feeds to a Rated-4 data center (ANSI/TIA-942)?

Options:

A.

Two feeds from two different substations, one power company not acceptable

B.

Two feeds from two different substations, one power company acceptable

C.

Two feeds from one substation

D.

One feed split into two distribution boards

Buy Now
Questions 24

The computer room has high levels of H2S gas contamination. What is the best option to resolve this issue?

Options:

A.

Vacuum the whole room using a HEPA/S-Class-based filter.

B.

Install air-scrubbers.

C.

Clean the room and racks with a damp/wet cloth.

D.

Provide more air changes per hour by adding more fresh air to the computer room.

Buy Now
Questions 25

A computer room is fitted with a hypoxic-based fire suppression system. On what principle does it work?

Options:

A.

It removes the heat from the fire

B.

It lowers the oxygen levels in the room

C.

It removes the fuel from the fire

D.

It uses water as an extinguisher

Buy Now
Questions 26

What is the risk of high levels of hydrogen sulfide (H₂S) in the computer room?

Options:

A.

There is no risk

B.

H₂S impacts the static properties of the floor

C.

H₂S can cause corrosion which impacts reliability of equipment

D.

H₂S impacts gas-based fire suppression system operation

Buy Now
Questions 27

What is the main advantage of using an End-of-Row (EoR) design?

Options:

A.

A single Top-of-Rack (ToR) switch is more expensive than an EoR switch

B.

You need a separate rack to install all your EoR switches

C.

There will be fewer switches to manage (corrected typing: original said “more”)

D.

A ToR switch has only optical interfaces

Buy Now
Questions 28

What is a potential disadvantage of using water mist as a fire extinguishing system?

Options:

A.

It only uses 10% of the water normally used in a water-based fire suppression, which might not be enough to suppress the fire

B.

It will rapidly increase the humidity level in the data center, which can cause a potential risk for the operation of the equipment

C.

It extracts oxygen from the air creating a potential risk for humans inside the computer room

D.

It has droplets that are too small (100-120 microns) so it can only be used for small fires

Buy Now
Questions 29

Can you install a raised floor tight to the perimeter of the room?

Options:

A.

Yes, but only if the data center is located in Zone 0 with no or little seismic activity

B.

Yes, a raised floor needs to be installed tight to the perimeter to prevent air leakage

C.

No, to avoid damage to the raised floor due to building and hygrothermal movement

D.

No, but this applies only to raised floors with a height of over 90 cm (3 ft)

Buy Now
Questions 30

The humidity in the computer room has changed from about 50% down to 35% Relative Humidity (RH).

What influence does this have on Electrostatic Discharge (ESD)?

Options:

A.

No influence as long as the temperature is at approximately 20°C/77°F

B.

Relative humidity has no influence on ESD

C.

ESD levels will go up

D.

ESD levels will go down

Buy Now
Questions 31

Smoke sensors must be installed in the computer room. What is the minimum density?

Options:

A.

1 per 5 m²

B.

1 per 10 m²

C.

1 per 25 m²

D.

1 per 40 m²

Buy Now
Questions 32

Two servers stacked with no gap (metal-to-metal). What heat transfer occurs?

Options:

A.

No heat transfer

B.

Conduction

C.

Radiation

D.

Convection

Buy Now
Questions 33

A data center is located in an area where the demand for power is higher than the utility power company is able to deliver. This results in frequent power outages and, therefore, power shedding (scheduled/controlled power shutdown for areas) is frequently applied. The mains power is more than 650 hours/year not available.

What type of generators should be installed?

Options:

A.

Standby generators should be installed in at least an N+1 configuration

B.

Continuous generators should be installed, at least in an N+1 configuration

C.

A combination of standby-, prime-, and continuous-generators, as the duration of the power outage is unpredictable. The total available capacity of the generators should be at least 500% of the data center load

D.

Continuous generators should be installed; no N+1 configuration is needed as the generators will run all the time

Buy Now
Questions 34

When installing a raised floor, can we use a spirit level bar to level the floor?

Options:

A.

Yes, spirit level bars can be used as long as their length is longer than 60 cm/2 ft (the size of a typical raised floor tile).

B.

No, because using a spirit level bar, a measurement error will be transferred from pedestal to pedestal.

C.

Yes, but spirit level bars can only be used in the vertical plane.

D.

Yes, using a spirit level bar for raised floors higher than 40 cm is preferred.

Buy Now
Questions 35

The 'maximum exposed area' of the fire-rated glass is defined by the supplier as 3 sqm/32 sqft. The window area is 4 sqm/43 sqft.

What would be the best option?

Options:

A.

Do not use fire-rated glass due to the size limit and replace it with normal glass.

B.

Split the window in two equal parts using an aluminum frame.

C.

Split the window into parts smaller than specified as the maximum exposed area and ensure fire-rated frames are used.

D.

Split the window in two equal parts fitted together with transparent silicon glue.

Buy Now
Questions 36

A data center requires an audit for ANSI/TIA-942 Rated-3 compliance. Will the network architecture be part of this audit?

Options:

A.

No, as concurrent maintainability only applies to electrical and mechanical

B.

No, only the type of cabling used will be audited

C.

Yes, but only if network administration does not comply with ANSI/TIA-606

D.

Yes, amongst other aspects the network architecture should be Rated-3 compliant with ANSI/TIA-942

Buy Now